Detail news
DRAWA: new medium voltage small switchboards
Elektromontaż Poznań System Manufacturing Plant have launched DRAWA medium voltage small switchboards for a range of industrial applications.
DRAWA is indoor switchgear engineered to receive and distribute three-phase alternate current of 24 kV rated voltage and 50 Hz frequency in industrial and dedicated power networks. DRAWA can be well fitted at contained transformer stations and local medium voltage distribution centres. Compact size make DRAWA switchgears a second to none solution for new or upgraded power facilities of limited extension room.
Characteristics of DRAWA switchgears include:
1. compartment arrangement
2. single busbar arrangement
3. steel housing
4. air jacket
5. steel partitions
6. gas insulated terminals
8. arc protection
State-of-the-art engineering combined with simple arrangements ensure easy operation, maintenance, and outstanding safety parameters. Multiple fields of different main circuit instrumentation have been provided for versatile applications and various customized configurations of multiple DRAWA switchboards.
DRAWA switchgears are combined of distributing fields equipped with instrumentation as required for the segment’s function within the dispatch arrangement. State-of-the-art terminal connectors are provided to ensure enormous reliability.
Each field is made of zinc or alu-zinc plated steel sheets for enhanced corrosion resistance. Doors, covers, and outer shields are powder painted.
Robust field structure ensures longevity and protection against inner electric arc.
Steel covers release if activated by the pressure of the gas generated during electric arc combustion.
DRAWA switchgear parameters:
Rated voltage | 12 kV / 17.5 kV / 24 kV | |
Surge withstand voltage | 75 kV / 95 kV / 125 kV | |
Withstand voltage 1 min 50 Hz | 28 / 42* kV / 38 kV / 50 kV | |
Rated frequency | 50 Hz | |
Phases | 3 | |
Rated continuous current | 630, 1250 A | |
Rated peak withstand current | 50 kA | |
Short-time withstand current (1 s) | 20 kA | |
Arc resistance | 20 kA / 1 s. | |
Busbar arrangement | single | |
Dimensions | ||
Height | 1700 (+200**) mm | |
Width | 375, 500, 600, 750 mm | |
Depth | 1000 (+220***, +80****) mm | |
Protection class | do IP-54 |
*) Requirements according to ΓOCT 14693:1990 standard
**) Low voltage
***) Switch-off drive
****) Disconnector drive